Yaskawa monitor/control object 125 (class 0x7d), Services supported, Attributes supported – Yaskawa SI-EN3D User Manual

Page 51

Advertising
background image

Instance

ID

Attribute

Name

Description

Get

Set

Size

Range

Default

...

...

...

...

...

O

Word

255

YY

MEMOBUS/

Modbus

Registers

0xFF00 to

0xFFFF

MEMOBUS/Modbus Registers

0xFF00 to 0xFFFF

O

O

Word

Note:

1. Attempting to set a read-only parameter results in an EtherNet/IP error code of 0x0E, Attribute Not Settable.
2. Attempting to access an invalid parameter results in an EtherNet/IP error code of 0x09, Invalid Attribute Value.
3. Refer to the MEMOBUS/Modbus Data Table in the MEMOBUS/Modbus Communications chapter of the drive manual for a list of

monitor data using the MEMOBUS/Modbus message area.

u

Yaskawa Monitor/Control Object 125 (Class 0x7D)

n

Services Supported

Service Code No. (Hex)

Service Name

0E

Get Attribute Single

10

Set Attribute Single

This is a dynamic explicit Class Object. With this Class object any parameter with a MEMOBUS/Modbus address less than

0x0100 can be accessed. This class is similar to the Drive Parameters Object Class 100, Object Class 100 differs slightly from

Object Class 125. In Object Class 125 the most significant byte of MEMOBUS/Modbus address is always zero and the Instance

ID remains at 1.
Given a typical MEMOBUS/Modbus Address 0f 0x00YY
The EtherNet/IP Instance value is equal to 0x01
The EtherNet/IP Attribute value is equal to YY
As an example, to access Drive Status (MEMOBUS/Modbus Address = 0x002C)
Class Object is 125 (0x7D) (Always for this Class Object)
Instance = 0x01
Attribute = 0x2C

n

Attributes Supported

Instance

ID

Attribute

MEMOBUS/

Modbus

Address

Description

Get

Set

Size

Range

Default

0

1

Object Software Revision

O

Word

1

1

1

0x0001

Drive Command Bits

O

O

Word

0

1

2

0x0002

Frequency Instruction

O

O

Word

4

..

..

..

..

O

O

Word

1

255

0x00FF

Unused

O

O

Word

Note:

1. Attempting to set a read-only parameter results in an EtherNet/IP error code of 0x0E, Attribute Not Settable.
2. Attempting to access an invalid parameter results in an EtherNet/IP error code of 0x09, Invalid Attribute Value.
3. Refer to the MEMOBUS/Modbus Data Table in the MEMOBUS/Modbus Communications chapter of the drive manual for a list of

monitor data using the MEMOBUS/Modbus message area.

11 Vendor-Specific (Yaskawa) Class Objects

YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual

51