Yaskawa SI-EN3D User Manual

Page 28

Advertising
background image

Name

Description

External Fault

External Fault EF0

0: No External Fault (EF0)

1: External Fault (EF0)

Fault Reset

Fault Reset

0: No Fault Reset

1: Fault Reset

Multi-Function Digital

Output

Terminal M1/M2

0: M1/M2 OFF

1: M1/M2 ON

This function is enabled only when H2-01 is set to F.

Multi-Function

Photocoupler 1

Terminal P1

0: P1 OFF

1: P1 ON

This function is enabled only when H2-02 is set to F.

Multi-Function

Photocoupler 2

Terminal P2

0: P2 OFF

1: P2 ON

This function is enabled only when H2-03 is set to F.

Speed Reference

Speed Command

Sets drive speed reference.
Unit depends on o1-03.

Unit is not affected by Speed Scale SS.

Torque Reference/Torque

Limit

Torque Reference/Torque Limit

Sets the Torque Reference/Torque Limit in units of 0.1%.

Sets the Torque Reference when using Torque Control (d5-01 = 1).

Sets the Torque Limit when using Speed Control (d5-01 = 0).

The Torque Reference and Torque Limit are disabled with F6-06 = 0.

Torque Compensation

Sets the amount of Torque Compensation Sets in units of 0.1%.

Digital Inputs

MEMOBUS/Modbus (0x49). Monitor parameter U1-10

NetRef

Network sets reference

NetCtrl

Network sets control

Analog Output 1

MEMOBUS/Modbus (0x0007)

Analog Output 2

MEMOBUS/Modbus (0x0008)

Digital Outputs

MEMOBUS/Modbus (0x0009)

Programmable Bytes

Contains the data to be written to the MEMOBUS/Modbus address defined in the given parameter. A value of 0 in the given

parameter means it is not used, therefore the value received for this given parameter will not be written to any MEMOBUS/

Modbus register. If the PPA is Input Assembly 166, then any errors occurring during a write will be flagged.

Refer to High

Speed/Torque Status Input (Vendor Specific Yaskawa Electric (YE) Assy) - 166 (0xA6) on page 36

for details.

8 Output Assemblies (Drive Consumes)

28

YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual

Advertising