Input assemblies (drive produces), Basic speed control input - 70 (0x46), Extended speed control input - 71 (0x47) – Yaskawa SI-EN3D User Manual

Page 29: 9input assemblies (drive produces)

Advertising
background image

9

Input Assemblies (Drive Produces)

Note:

The convention in this manual is from the PLC perspective. An “Input Assembly” is outputted from this node and read by the PLC. This

section details “Input Assemblies” that are “Produced” by this drive.

u

Basic Speed Control Input - 70 (0x46)

Input Instance

Word

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

70

0

0

Running 1

(FWD)

Faulted

1

1

2

Speed Actual (Low Byte)

3

Speed Actual (High Byte)

Name

Description

Faulted

Faulted

0: No Faults Occurred

1: Fault Occurred

Running 1 (FWD)

Forward Running

0: Stop or Reverse Running

1: Forward Running

Speed Actual

Actual Drive Speed

Monitors drive output frequency.

Speed actual data: Output frequency x 2

SS

(SS: Speed scale)

Setting range: 0 to 0xFFFF

For example, when output frequency of 1024 with a speed scale of 2:

Speed actual data = 1024 x 2

2

= 4096 = 0x1000

Unit depends on o1-03.

u

Extended Speed Control Input - 71 (0x47)

Input Instance

Word

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

71

0

0

At Speed

Ref from

Net

Ctrl from

Net

Ready

Running 2

(REV)

Running 1

(FWD)

Warning

Faulted

1

Drive State

1

2

Speed Actual (Low Byte)

3

Speed Actual (High Byte)

Name

Description

Faulted

Faulted

0: No Faults Occurred

1: Fault Occurred

Warning

Warning

0: No Warning Occurred

1: Warning Occurred

Running 1 (FWD)

Forward Running

0: Stop or Reverse Running

1: Forward Running

Running 2 (REV)

Reverse Running

0: Stop or Forward Running

1: Reverse Running

Ready

Drive Ready

0: Not Ready

1: Ready

Ctrl from Net

Status of Run command from Network

0: Run command is not from network

1: Run command is from network

Ref from Net

Status of Speed reference from Network

0: Speed reference is not from network

1: Speed reference is from network

At Speed

Speed Agree

0: No Speed Agree

1: Speed actual at speed reference

9 Input Assemblies (Drive Produces)

YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual