Name

Description

Running 2 (REV)

Reverse Running

0: Stop or Forward Running

1: Reverse Running

Ready

Drive Ready

0: Not Ready

1: Ready

Ctrl from Net

Status of Run command from Network

0: Run command is not from network

1: Run command is from network

Ref from Net

Status of Speed reference from Network

0: Speed reference is not from network

1: Speed reference is from network

At Speed

Speed Agree

0: No Speed Agree

1: Speed actual at speed reference

Drive State

Contains the value from the Control Supervisor (Class 0x29) Instance 1 Attribute 6.

Speed Actual

Actual Drive Speed

Monitors drive output frequency.

Speed actual data: Output frequency x 2

SS

(SS: Speed scale)

Setting range: 0 to 0xFFFF

For example, when output frequency of 1024 with a speed scale of 2:

Speed actual data = 1024 x 2

2

= 4096 = 0x1000

Unit depends on o1-03.

Torque Actual

Output Torque

Shows the Torque Reference.

Value displays in 0.1% units.

u

MEMOBUS/Modbus Message Input (Vendor Specific Yaskawa Electric (YE) Assy) - 150
(0x96)

Input Instance

Word

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

150

0

0

Function Code

1

Register Number (High Byte)

1

2

Register Number (Low Byte)

3

Register Data (High Byte)

2

4

Register Data (Low Byte)

Note:

This is a paired assembly (100/150).

Table 9 Reply Mapping – 150

Byte

Write Success

Read Success

Write Failure

Read Failure

Invalid Function Code Function Code

Equals Zero

0

0x10

0x03

0x90

0x83

Function Code Or-ed with

0x80

0

1

Output Assembly

Register Number

(High Byte)

Output Assembly

Register Number

(High Byte)

Output Assembly

Register Number

(High Byte)

Output Assembly

Register Number

(High Byte)

Output Assembly

Register Number

(High Byte)

0

2

Output Assembly

Register Number

(Low Byte)

Output Assembly

Register Number

(Low Byte)

Output Assembly

Register Number

(Low Byte)

Output Assembly

Register Number

(Low Byte)

Output Assembly

Register Number

(Low Byte)

0

3

0

Read Data

(High Byte)

0

0

0

0

4

0

Read Data (Low Byte)

Error Code

Error Code

1

0

Table 10 Error Replies – 150

Error Code

Description

0x01

Invalid Function Code

0x02

Invalid Register Number

0x21

Upper/Lower Limit Error

9 Input Assemblies (Drive Produces)

YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual

31