Yaskawa SI-EN3D User Manual

Page 39

Advertising
background image

Name

Description

F7-38 PG Count Value

(CH 2)

Programmable: MEMOBUS/Modbus (0xF1)

Serial interface Control Response

F7-39 NetRef (Status)

Status of reference command from Network

0: Reference command is not from network

1: Reference command is from network

F7-40 Drive Software

Version

Programmable: MEMOBUS/Modbus (0x4D)

Monitor parameter U1-25

Possible extended error codes are listed in

Table 11

and

Table 12

. If an error occurs, extended error code 0x02 (Register

number failure) is usually set.

Table 11 Extended Error Codes for Assembly 116/166

Error Code

Description

0x00

No error

0x01

Sub function code failure

0x02

Register number failure

0x21

Limit check error failure

0x22

Write failure

0x23

Write failure at Uv

0x24

Write failure at busy

Table 12 Extended Error Codes in Class 0x04 Instance 0xA6 Attribute 0x64

Dynamic Parameter

Byte Containing Extended Error Code

F7-23

Byte 0

F7-24

Byte 1

F7-25

Byte 2

F7-26

Byte 3

F7-27

Byte 4

F7-28

Byte 5

F7-29

Byte 6

F7-30

Byte 7

F7-31

Byte 8

F7-32

Byte 9

F7-33

Byte 10

F7-34

Byte 11

F7-35

Byte 12

F7-36

Byte 13

F7-37

Byte 14

F7-38

Byte 15

F7-39

Byte 16

F7-40

Byte 17

F7-41

Byte 18

F7-42

Byte 19

9 Input Assemblies (Drive Produces)

YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual

39