Fault codes, Major fault – Yaskawa GPD 506/P5 Section Three User Manual

Page 10

Advertising
background image

PP.P5G5.03.Troubleshoot

Page 10

Rev. 06/11/2003

Inverter input power supply has an open phase.
Large imbalance of input voltage.

PF

Input Pha Loss

sp

1

Inverter output has an open phase.

LF

Output Pha Loss

sp

o

Possible Cause(s):

Open phase on the input of the inverter. Loose terminal screws at

terminals L1, L2, or L3. Program parameters set incorrectly (n083 for 506/P5, L8-05 for 515/G5)

Corrective Action:

Tighten the terminal screws, check the input voltage, verify the program

settings.

Possible Cause(s):

Open phase on the output of the inverter. Loose terminal screws at

terminals T1, T2, or T3. Program parameters set incorrectly.

Corrective Action:

Tighten the terminal screws, check the output voltage, verify the

program settings.

Fault Codes

Major Fault

- Motor coasts to a stop, the fault is displayed on the digital

operator, and the fault relay is activated.

505

506

515

506

515

505