Fault codes, Major fault – Yaskawa GPD 506/P5 Section Three User Manual

Page 11

Advertising
background image

PP.P5G5.03.Troubleshoot

Page 11

Rev. 06/11/2003

The motor speed has exceeded the overspeed level

when operating in the Closed Loop V/f or Closed

Loop Flux Vector modes.

OS

Overspeed Det

N/A

Feedback pulses are not received by the PG option

board.

PGO

PG open

N/A

Possible Cause(s):

The load has changed considerably, the program settings may not be

set correctly.

Corrective Action:

Check the load on the motor, verify the program settings (F1-08 PG

Overspeed Level, and F1-09 PG Overspeed Time).

Possible Cause(s):

The Pulse Generator feedback wires may be broken or not properly

connected to the PG feedback option board.

Corrective Action:

Check for a broken wire or a loose connection from the Pulse

Generator, verify the program settings.

505

Fault Codes

Major Fault

- Motor coasts to a stop, the fault is displayed on the digital

operator, and the fault relay is activated.

506

515

505

506

515