The actual torque during deceleration has reached

the regen torque limit for more than 3 seconds.

(Open Loop Flux Vector mode only)

CF

Out of Control

N/A

In the zero servo mode, the motor shaft has

rotated 10,000 non-quadrature PG pulses from the

home position.

SVE

Zero Servo Fault

N/A

Possible Cause(s):

The regen torque limit value is set too low, load torque is excessively

large.

Corrective Action:

Verify the program setting, L7-03 forward regen torque limit and L7-04

reverse regen torque limit, extend the deceleration time.

Possible Cause(s):

Torque limit or zero servo gain set too low, load torque excessively

large, PG signal noise.

Corrective Action:

Verify the program parameters B9-01 zero servo gain and torque limit

settings L7-01 ~ L7-02, check for noise on the PG signals.

505

Fault Codes

Major Fault

- Motor coasts to a stop, the fault is displayed on the digital

operator, and the fault relay is activated.