PP.P5G5.03.Troubleshoot

Page 5

Rev. 06/11/2003

The pre-charge contactor opened while the inverter is

running.

UV3

MC Answerback

U

u

3

Overvoltage of the main circuit when running.
230V Units - trip point 400V DC or more.
460V Units - trip point 800V DC or more.
600V Units - trip point 1050V DC or more.

OV

DC Bus Overvolt

ou

„

This fault only applies to 230V units 18kW ~ 75kW , 460V units 22kW ~ 160kW and

600V units 30kW ~ 160kW .

Possible Cause(s):

Contacts on contactor are dirty, contactor does not function mechanically.

Corrective Action:

Check the contactor, check the ribbon cable from the control board to the

gate drive board.

Possible Cause(s):

High input voltage at L1, L2, and L3. The deceleration time is set too

short. Power factor correction capacitors are being used on the input to the inverter.

Corrective Action:

Check the input circuit, verify the program parameters, add a braking

resistor, remove the power factor correction capacitors.

505

Fault Codes

Major Fault

- Motor coasts to a stop, the fault is displayed on the digital

operator, and the fault relay is activated.

506

515