Designed to protect the inverter.
Output current has exceeded OC level of the inverter

rated value instantaneously.

OC

Over current

oc

Designed to protect the inverter.

Inverter output grounding current has exceeded 50%
of the inverter rated current.

GF

Ground Fault

gf

Possible Cause(s):

Shorted inverter output phase to phase, shorted motor, locked rotor.

Corrective Action:

Remove the motor and run the inverter without the motor. Check the

motor for a phase to phase short. Check the inverter for a phase to phase short at the output.

Possible Cause(s):

Motor lead shorted to ground, DCCT defective.

Corrective Action:

Remove the motor and run the inverter without the motor. Check the

motor for a phase to ground short. Check the output current with a clamp on meter to verify the
DCCT reading.

505

Fault Codes

Major Fault

- Motor coasts to a stop, the fault is displayed on the digital

operator, and the fault relay is activated.

OC – 200%

20P4 – 2015

40P4 – 4015

51P5 - 5160

OC – 180%

2018 – 2075

4018 – 4160

506

515