Fault codes, Major fault – Yaskawa GPD 506/P5 Section Three User Manual

Page 7

Advertising
background image

PP.P5G5.03.Troubleshoot

Page 7

Rev. 06/11/2003

The inverter output is short-circuited.

SC

Short Circuit

sc

Detects if the DC bus fuse has opened.

PUF

DC Bus Fuse Open

PUf

Possible Cause(s):

Shorted output transistor, shorted main circuit component.

Corrective Action:

Remove power from the inverter and disconnect the motor. Perform the

checks without/with power starting on page 10. Replace the shorted component(s), then
replace the defective fuse.

505

Possible Cause(s):

Shorted inverter output phase to phase, shorted motor, locked rotor.

Corrective Action:

Remove the motor and run the inverter without the motor. Check the

motor for a phase to phase short. Check the inverter for a phase to phase short at the output.

Fault Codes

Major Fault

- Motor coasts to a stop, the fault is displayed on the digital

operator, and the fault relay is activated.

506

515