CPF00

Com-Err(OP&INV)

Transmission between the inverter and the operator
cannot be established 5 seconds after supplying
power.

cpf0

Possible Cause(s):

Digital operator cable not securely connected, digital operator

defective, control board defective.

Corrective Action:

Check the operator cable, replace the digital operator, replace the

control board.

CPF01

Com-Err(OP&INV)

Communication fault between the inverter and the
operator has occurred for more than 2 seconds.

cpf1

Possible Cause(s):

Digital operator cable not securely connected, digital operator

defective, control board defective.

Corrective Action:

Check the digital operator cable, replace the digital operator, replace

the control board.

505

Fault Codes

Major Fault

- Motor coasts to a stop, the fault is displayed on the digital

operator, and the fault relay is activated.