Motor overload, designed to protect the motor.
Fully adjustable from parameter setting (n033 and

n034 for 506/P5 and E1-02 and E2-01 for 515/G5)

A pre-alarm can be selected as a minor fault by using
the multi-function outputs.

OL1

Motor Overloaded

o

l1

Inverter overload, designed to protect the inverter.
120 or150% of inverter rated current for 1 minute.

515 - 150% for 1 minute

505 and 506 - 120% or 150% depending on drive
capacity and setting parameter n116

OL2

Inv Overloaded

o

l2

Possible Cause(s):

Motor is overloaded.

Corrective Action:

Verify the program settings, reduce the load on the motor.

Possible Cause(s):

Motor is overloaded.

Corrective Action:

Verify the program settings, reduce the load on the motor.

505

Fault Codes

Major Fault

- Motor coasts to a stop, the fault is displayed on the digital

operator, and the fault relay is activated.