Fault Codes

Parameter Setting Error

- Inverter can’t run. The fault is displayed

on the digital operator, and the fault relay is not activated.

Inverter kVA setting error.

OPE01

kVA Selection

ope 1

OPE02

Limit

Constant data is out of range. 506 digital operator will

display OPE06.

ope 6

Possible Cause(s):

The control board was replaced and the kVA parameter is set incorrectly.

Corrective Action:

Enter the correct kVA setting (O2-4 for GPD515/G5) and (n115 for

GPD506/P5) by referring to the inverter model number.

Possible Cause(s):

Parameter set above the allowable range.

Corrective Action:

Verify the program settings.