Fault Codes

Parameter Setting Error

- Inverter can’t run. The fault is displayed

on the digital operator, and the fault relay is not activated.

Closed Loop Flux Vector mode has been selected

without a PG board installed.

OPE06

PG Opt Missing

Possible Cause(s):

PG option board not correctly installed or missing. The control method

selection parameter A1-02 is set to 1 or 3 without a feedback board installed.

Corrective Action:

Verify that an option board is installed. Remove power to the inverter

and connect the option board once more.

OPE07

Analog Selection

The multi-function analog inputs terminals 14 and

16 are set for the same function.

Possible Cause(s):

Duplicate functions are selected.

Corrective Action:

Verify the set values of H3-09 (terminal 14 selection) and H3-05

(terminal 16 selection).