Fault Codes

Parameter Setting Error

- Inverter can’t run. The fault is displayed

on the digital operator, and the fault relay is not activated.

OPE11

FC/ On-Dly

Carrier frequency data setting fault.

Upper limit (C6-01) >5KHz, and the lower limit
(C6-02) <= 5KHz.

Carrier frequency proportional gain (C6-03) > 6 and
(C6-01) < (C6-02).

N/A

Possible Cause(s):

Parameter setting incorrect.

Corrective Action:

Check the program settings and correct the errors.

Possible Cause(s):

Connection not made properly, user software not configured to the

proper baud rate or configuration.

Corrective Action:

Check all connections, verify all user side software configurations.

CALL

Serial Com Call

Serial communication transmission error.
Communication has not yet been established.

call

505

506

515

505

506

515