Fault Codes

Minor Fault

- Operation continues and the digital operator indication blink

The fault relay does not activate.

The main circuit or control circuit voltage has fallen
below the under voltage trip point momentarily.

A minor fault contact output can be programmed by
using the multi-function outputs. (GPD515/G5 only)

UV

DC Bus Undervolt

U

u

The DC bus voltage has exceeded the overvoltage
trip point while the inverter output is off.

OV

DC Bus Overvolt

ou

Possible Cause(s):

Single phase condition on the input, low input voltage at L1, L2, and L3.

Corrective Action:

Check the three phase input voltage, verify setting of L2-05 for GPD515/G5

Possible Cause(s):

High input voltage at L1, L2, and L3. Power factor correction

capacitors are being used on the input to the inverter.

Corrective Action:

Check the input circuit, verify the program parameters, add a braking

resistor, remove power factor correction capacitors.