Fault codes, Parameter setting error, Ope 5 – Yaskawa GPD 506/P5 Section Three User Manual

Page 37

Advertising
background image

PP.P5G5.03.Troubleshoot

Page 37

Rev. 06/11/2003

Fault Codes

Parameter Setting Error

- Inverter can’t run. The fault is displayed

on the digital operator, and the fault relay is not activated.

Multi-function input or multi-function output data

setting error.

OPE08

Terminal

Possible Cause(s):

A multi-function selection has been chosen that is not offered in the

present control mode.

Corrective Action:

Check the “modified constants” area and verify the set values in

parameters H1-01~H1-06, H2-01~H2-03, H3-05, H3-09, H4-01 and H4-04.

V/F data setting fault. 506 digital operator will display

OPE10.

OPE10

V/F Ptrn Setting

Possible Cause(s):

The V/f parameter settings are not set correctly.

Corrective Action:

Check parameters (E1-04 ~ E1-11) for the 515/G5 and parameters

(n012 ~ n018) for the 506/P5. A minimum frequency/voltage value may be set higher than the
maximum frequency/voltage.

ope 5

N/A

505

506

515

505

506

515