Fault Codes

Parameter Setting Error

- Inverter can’t run. The fault is displayed

on the digital operator, and the fault relay is not activated.

Possible Cause(s):

Serial communication option board is not installed, option board is

installed incorrectly. The run command selection parameter B1-02 is set to 3 and option board
is not installed.

Corrective Action:

Verify that an option board is installed. Remove power to the inverter

and connect the option board once more.

OPE03

Terminal

Multi-function input selection fault.

ope 3

Possible Cause(s):

Duplicate functions are selected, up/down commands or trim control

increase/decrease are not set simultaneously (GPD515/G5 only). Speed search from maximum
frequency and speed search from set frequency are set simultaneously.

Corrective Action:

Verify program settings 515/G5 (H1-01 ~ H1-06), 506/P5 (n035 ~ n039).

OPE05

Sequence Select

Run command is selected through serial

communication at 2CN but option board is not

installed.