PP.P5G5.03.Troubleshoot

Page 14

Rev. 06/11/2003

o

h2

The transistor cooling fin temperature exceeded the
allowable value. 506/P5 (105 ° C), 515/G5 (105 ° C)

OH1

Heatsnk MAX Temp

Possible Cause(s):

Cooling fan(s) are not working, high ambient temperature.

Corrective Action:

Check for dirt build-up on the fans, reduce the ambient temperature

around the inverter.

505

Fault Codes

Major Fault

- Motor coasts to a stop, the fault is displayed on the digital

operator, and the fault relay is activated.

The inverter will stop if the digital operator is removed

when the inverter is commanded to run through the

digital operator.

OPR

Oper Disconnect

Possible Cause(s):

The operator is not attached, broken operator cable.

Corrective Action:

Attach the digital operator, check the cable connected to the digital operator,

verify the program setting of parameter O2-06 for 515/G5 models and n112 for 506/P5 models.

o

p

506

515