WARNING! Crush Hazard. Use an adequate length of wire to ensure a 50° or wider suspension angle as illustrated in

Figure i.10

. The

maximum allowable load of the eye bolts cannot be guaranteed when the drive is suspended with the wires at angles less than 50°. Failure

to comply may result in serious injury or death from falling equipment.

1. Remove the two hanging brackets from the drive lower side panels and bolt them on the top panel.

Note:

1. Tighten the hanging brackets with the specified tightening torque: M10: 18 to 23 N·m (159 to 204 in-lb),

M12: 32 to 40 N·m (283 to 354 in-lb).

2. Four hanging brackets are attached to the top of NEMA Type 1 drives 2o0154F, 2o0192F, 4o0156F, and 4o0180F.

Figure i.10 Location of Hanging Brackets (Models 2o0154 to 2o0248 and 4o0156 to 4o0414)

2. Pass wire through the holes of all four hanging brackets.

Suspending angle:
50° or greater

Figure i.11 Drive Suspension Using Wires and Hanging Brackets (Models 2o0154 to 2o0248 and 4o0156 to 4o0414)

3. Gradually take up the slack in the wires and hoist the drive after the wires are stretched tight.
4. Lower the drive when ready to install in the enclosure panel. Stop lowering the drive when it is near the floor, then slowly

begin lowering the drive again until the drive is placed correctly.

u

Drive Dimensions

NOTICE

Refer to the U1000 Industrial MATRIX Drive Technical Manual SIEP C710636 04 for IP20/NEMA Type 1 and IP00/Open
Chassis dimensions.
The U1000 Industrial MATRIX Drive Technical Manual is posted on the Yaskawa website, www.yaskawa.com.

i.3 Mechanical Installation