Parameter table, I.8 parameter table – Yaskawa U1000 Industrial MATRIX Drive User Manual

Page 77

Advertising
background image

i.8

Parameter Table

This parameter table shows the most important parameters. Default settings are in bold type. Refer to the Technical Manual

for a complete list of parameters.

No.

Name

Description

A1-02

Control Method

Selection

0: V/f Control

1: V/f Control with PG

2: Open Loop Vector Control

3: Closed Loop Vector Control

5: Open Loop Vector Control for PM

6: Advanced Open Loop Vector Control for

PM

7: Closed Loop Vector Control for PM

A1-03

Initialize Parameters

0: No initialization

1110: User Initialize (parameter values

must be stored using parameter o2-03)

2220: 2-Wire initialization

3330: 3-Wire initialization

5550: oPE04 error reset

A1-06

Application Preset

0: General-purpose

1: Water supply pump

2: Conveyor

3: Exhaust fan

4: HVAC fan

5: Air compressor

b1-01

Frequency Reference

Selection 1

0: Digital operator

1: Analog input terminals

2: MEMOBUS/Modbus communications

3: Option PCB

4: Pulse train input (terminal RP)

b1-02

Run Command

Selection 1

0: Digital operator

1: Digital input terminals

2: MEMOBUS/Modbus communications

3: Option PCB

b1-03

Stopping Method

Selection

0: Ramp to stop

1: Coast to stop

2: DC Injection Braking to stop

3: Coast with timer

b1-04

Reverse Operation

Selection

0: Reverse enabled.

1: Reverse disabled.

C1-01

Acceleration Time 1

Sets the time to accelerate from 0 to

maximum frequency.

C1-02

Deceleration Time 1

Sets the time to decelerate from maximum

frequency to 0.

C2-01

S-Curve Characteristic

at Accel Start

S-curve at acceleration start.

C2-02

S-Curve Characteristic

at Accel End

S-curve at acceleration end.

C2-03

S-Curve Characteristic

at Decel Start

S-curve at deceleration start.

C2-04

S-Curve Characteristic

at Decel End

S-curve at deceleration end.

C6-01

Drive Duty Selection

0: Heavy Duty (HD)

Overload capability: 150% of drive rated

Heavy Duty current for 60 s

Default Carrier Frequency: 2 kHz

1: Normal Duty (ND)

Overload capability: 120% of drive rated

Normal Duty current for 60 s

Default Carrier Frequency: 2 kHz Swing

PWM

No.

Name

Description

C6-02

Carrier Frequency

Selection

1: 4.0 kHz

2: 6.0 kHz

3: 8.0 kHz

4: 10.0 kHz

F: User-defined (determined by C6-03 to

C6-05)

Default setting value is determined by

A1-02, Control Method Selection, C6-01,

Drive Duty Selection, and o2-04, Drive

Model Selection.

C7-60

Output Voltage Limit

Mode Selection

0: Harmonic suppression priority mode

1: High output voltage mode

d1-01 to

d1-16

Frequency Reference 1

to 16

Sets the frequency reference for the drive.

Setting units are determined by parameter

o1-03.

d1-17

Jog Frequency

Reference

Sets the Jog frequency reference. Setting

units are determined by parameter o1-03.

d2-01

Frequency Reference

Upper Limit

Sets the frequency reference upper limit as

a percentage of the maximum output

frequency.

d2-02

Frequency Reference

Lower Limit

Sets the frequency reference lower limit as

a percentage of the maximum output

frequency.

E1-03

V/f Pattern Selection

0: 50 Hz, Constant torque 1

1: 60 Hz, Constant torque 2

2: 60 Hz, Constant torque 3 (50 Hz base)

3: 72 Hz, Constant torque 4 (60 Hz base)

4: 50 Hz, Variable torque 1

5: 50 Hz, Variable torque 2

6: 60 Hz, Variable torque 1

7: 60 Hz, Variable torque 2

8: 50 Hz, High starting torque 1

9: 50 Hz, High starting torque 2

A: 60 Hz, High starting torque 3

B: 60 Hz, High starting torque 4

C: 90 Hz (60 Hz base)

D: 120 Hz (60 Hz base)

E: 180 Hz (60 Hz base)

F: Custom V/f, E1-04 through E1-13

settings define the V/f pattern

E1-04

Maximum Output

Frequency

Parameters E1-04 and E1-06 to E1-13 can

only be changed when E1-03 is set to F.

To set linear V/f characteristics, set the

same values for E1-07 and E1-09.

In this case, the setting for E1-08 will be

disregarded. Ensure that the five

frequencies are set according to the

following rules to prevent triggering an

oPE10 fault:

E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04

Setting E1-11 to 0 disables both E1-11 and

E1-12 and the above conditions do not

apply.

Output Voltage (V)

Frequency (Hz)

E1-05
E1-12

E1-13

E1-08

E1-10

E1-09

E1-07 E1-06 E1-11 E1-04

E1-05

Maximum Voltage

E1-06

Base Frequency

E1-07

Middle Output

Frequency

E1-08

Middle Output

Frequency Voltage

E1-09

Minimum Output

Frequency

E1-10

Minimum Output

Frequency Voltage

E1-11

Middle Output

Frequency 2

E1-12

Middle Output

Frequency Voltage 2

E1-13

Base Voltage

i.8 Parameter Table

YASKAWA ELECTRIC TOEP C710636 04C U1000 Industrial MATRIX Drive Quick Start Guide

77