Overload Tolerance

Cooling Ability

Overload Characteristics

Percent of base speed (%)

0 0.2

100

130

150

150

100

115

77
67

Instantaneous rating (60 s)

125

83

120

Continuous

Torque (%)

Motor is designed to effectively cool

itself at speeds near 0.2% of base

speed.

Continuous operation with 100% load

from 0.2% to 100% of base speed.

Setting 6: General-purpose Motor

Note:

General-purpose motors are designed with a base speed that operates at line frequency (50/60 Hz depending on geographic region).

Because the motor is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive appropriately

adjusts the electrothermal trigger point according to the motor overload characteristics and protects the motor from overheat

throughout the entire speed range.

Overload Tolerance

Cooling Ability

Overload Characteristics

A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
C: Max. speed for 132MJ and below

05 33 100 120 167 200

Speed (%)

Continuous

A

B

C

Rated Speed=100% Speed

60 s

150

100

90

60

50

Torque (%)

Motor designed to operate from line

power. Motor cooling is most effective

when running at rated base frequency

(check the motor nameplate or

specifications)

Continuous operation at less than line

power frequency with 100% load can

trigger a motor overload fault (oL1). A

fault is output and the motor will coast

to stop.

n

L1-02: Motor Overload Protection Time

Sets the time for the drive to shut down on motor overload (oL1) when the motor is running with excessive current. Enter the

time the motor can withstand operating at 150% current after previously running at 100% current (hot motor overload

condition). There is normally no need to change this parameter from the default value.

No.

Name

Setting Range

Default

L1-02

Motor Overload Protection Time

0.1 to 5.0 minutes

1.0 minutes

Defaulted to operate with an allowance of 150% overload operation for one minute in a hot start after continuous operation

at 100%.

Figure i.47

illustrates an example of the electrothermal protection operation time using a general-purpose motor operating at

the value of E1-06, Motor Base Speed, with L1-02 set to one minute.
Motor overload protection operates in the area between a cold start and a hot start.
• Cold start: Characteristics of motor protection operation time in response to an overload situation that was suddenly reached

when starting a stationary motor.

• Hot start: Characteristics of motor protection operation time in response to an overload situation that occurred while the

motor was operating continuously at or below its rated current.

i.5 Start-Up Programming and Operation

60