Specifications

The Safe Disable inputs provide a stop function in compliance with “Safe Torque Off” as defined in the IEC/EN 61800-5-2.

Safe Disable inputs have been designed to meet the requirements of the ISO/EN 13849-1 and IEC/EN 61508.
A Safe Disable Status Monitor for error detection in the safety circuit is also provided.

Table i.32 Specifications for Safe Disable Function

Inputs/Outputs

• Input signal specifications

Signal ON level: 18 to 28 Vdc
Signal OFF level: -4 to 4 Vdc

• Inputs: 2

Safe Disable inputs H1, H2

• Outputs: 1

Safe Disable Monitor output EDM (DM+, DM-)

Response Time from Input Open to Drive

Output Stop

Shorter than 3 ms

Response Time from Input Open of H1 and H2

Terminals to EDM

Shorter than 4 ms

Failure Probability

Demand Rate Low

PFD = 8.14E

-6

Demand Rate High/

Continuous

PFH = 1.96E

-9

Performance Level

The Safe Disable inputs satisfy the following requirements (DC from EDM considered) Performance

Level (PL) e according to ISO/EN 13849-1

HFT (Hardware Fault Tolerance)

N = 1

Classification of Subsystem

Type B

u

Precautions

DANGER! Sudden Movement Hazard. Improper use of the Safe Disable function can result in serious injury or even death. Make sure the

whole system or machinery in which the Safe Disable function is used complies with safety requirements. When implementing the Safe

Disable function into the safety system of a machine, perform a thorough risk assessment for the entire system to assure compliance with

relevant safety norms.

DANGER! Sudden Movement Hazard. When using a PM motor, even if the drive output is shut off by the Safe Disable function, a breakdown

of two output transistors can cause current to flow through the motor winding, resulting in a rotor movement for a maximum angle of 180

degrees (electrically). Make sure such a situation would have no effect on the safety of the application when using the Safe Disable function.

DANGER! Electrical Shock Hazard. The Safe Disable function can switch off the drive output, but does not cut the drive power supply and

cannot electrically isolate the drive output from the input. Always shut off the drive power supply when performing maintenance or installations

on the drive input side as well as the drive output side.

DANGER! Sudden Movement Hazard. The motor will move when an external gravitational force in the vertical axis is applied even if the

Safe Disable function is in operation. Failure to comply may result in serious injury or death.

DANGER! Sudden Movement Hazard. Connect the Safe Disable inputs to the devices in compliance with safety requirements. Failure to

comply will result in death or serious injury.

WARNING! Sudden Movement Hazard. When using the Safe Disable inputs, make sure to remove the wire links between terminals H1,

H2, and HC that were installed prior to shipment. Failing to do so will keep the Safe Disable circuit from operating properly and can cause

injury or even death.

NOTICE: All safety features (including Safe Disable) should be inspected daily and periodically. If the system is not operating normally,

there is a risk of serious personal injury.

NOTICE: Only a qualified technician with a thorough understanding of the drive, the instruction manual, and safety standards should be

permitted to wire, inspect, and maintain the Safe Disable input.

NOTICE: From the moment terminal inputs H1 and H2 have opened, it takes up to 2 ms for drive output to shut off completely. The sequence

set up to trigger terminals H1 and H2 should make sure that both terminals remain open for at least 2 ms in order to properly interrupt drive

output.

NOTICE: The Safe Disable Monitor (output terminals DM+ and DM-) should not be used for any other purpose than to monitor the Safe

Disable status or to discover a malfunction in the Safe Disable inputs. The monitor output is not considered a safe output.

NOTICE: When utilizing the Safe Disable function, an EMC filter must be used.

i.9 Standards Compliance

YASKAWA ELECTRIC TOEP C710636 04C U1000 Industrial MATRIX Drive Quick Start Guide