Auto-tuning errors – Yaskawa U1000 Industrial MATRIX Drive User Manual

Page 73

Advertising
background image

Digital Operator Display

Error Name

oPE08

Parameter Selection Error
A function has been set that cannot be used in the motor control method selected.

oPE09

PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is enabled (b5-01 = 1 to 4).

oPE10

V/f Data Setting Error
One or more of the parameters listed below are not set according to the formula:
• E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
• E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04

oPE11

Carrier Frequency Setting Error
Correct the setting for the carrier frequency.

oPE13

Pulse Monitor Selection Error
Incorrect setting of monitor selection for pulse train (H6-06).

oPE15

Torque Control Setting Error
Parameter settings that are not allowed in combination with Torque Control have been set.

oPE16

Energy Savings Constants Error

oPE18

Online Tuning Parameter Setting Error
Parameters controlling online tuning are not set correctly.

oPE20

PG-F3 Setting Error
The encoder signal frequency is too high.

oPE30

Incorrect Input Voltage Adjustment
The input voltage offset adjustment has not been performed.

u

Auto-Tuning Errors

n

Auto-Tuning Codes

Auto-Tuning faults in this section are displayed on the digital operator and will cause the motor to coast to a stop. Auto-Tuning

faults do not trigger a multi-function digital output set for fault or alarm output.
An Endo error on the digital operator display indicates Auto-Tuning has successfully completed with discrepancies in the

calculations. Restart Auto-Tuning after fixing the cause of the Endo error.
The drive may be used in the application if no cause can be identified despite the existence of an Endo error.
An Ero error indicates that Auto-Tuning has not completed successfully. Check for the cause of the error using the tables in

this section, and perform Auto-Tuning again after fixing the cause.

Digital Operator Display

Error Name

End1

Excessive V/f Setting (detected only during Rotational Auto-Tuning and displayed after Auto-Tuning is

complete)

End2

Motor Iron-Core Saturation Coefficient (detected only during Rotational Auto-Tuning and displayed after

Auto-Tuning is complete)

End3

Rated Current Setting Alarm (displayed after Auto-Tuning is complete)

End4

Adjusted Slip Calculation Error

End5

Resistance Tuning Error

End6

Leakage Inductance Alarm

End7

No-Load Current Alarm

Er-01

Motor Data Error

Er-02

Minor Fault

Er-03

STOP Button Input

Er-04

Line-to-Line Resistance Error

Er-05

No-Load Current Error

Er-08

Rated Slip Error

Er-09

Acceleration Error

Er-10

Motor Direction Error

i.6 Troubleshooting

YASKAWA ELECTRIC TOEP C710636 04C U1000 Industrial MATRIX Drive Quick Start Guide

73