Basic Start-Up and Motor Tuning Flowchart

The flowchart shown in

Figure i.33

describes a basic start-up sequence that varies slightly depending on the application. Use

the drive default parameter settings in simple applications that do not require high precision.

YES

NO

START

Properly install and wire the drive.

Apply main power to the drive while following safety guidelines.

Application Preset

A1-06 used?

Set the control mode in parameter A1-02.

Refer to
Application
Selection section

Set the basic parameters

b1-01/b1-02 for frequency reference selection and run command source selection

H1-oo,H2-oo,H3-oo,H4-oo,H6-oo for I/O terminal setting

d1-oo for using multi-speed references

C1-oo and C2-oo for accel/decel and S-curve time settings

C6-01 for heavy/normal duty mode selection

Fine tune parameters. Adjust application settings if necessary.

Check the machine operation and verify parameter settings.

Drive is ready to run the application.

Figure i.33 Basic Start-Up

n

Powering Up the Drive

Review the following checklist before turning the power on.

Item to Check

Description

Power supply voltage

200 V class: Three-phase 200 to 240 Vac 50/60 Hz

400 V class: Models 4Aoooo and 4Poooo: Three-phase 380 to 500 Vac 50/60 Hz

400 V class: Models 4Eooooand 4Woooo: Three-phase 380 to 480 Vac 50/60 Hz
Properly wire the power supply input terminals (R/L1, S/L2, T/L3).
Check for proper grounding of drive and motor.

Use a power supply with a capacity that is equal to or greater than drive capacity.

Drive output terminals and

motor terminals

Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, and W.

Control circuit terminals

Check control circuit terminal connections.

Drive control terminal status

Open all control circuit terminals (off).

Status of the load and connected

machinery

Decouple the motor from the load.

u

Basic Drive Setup Adjustments

n

A1-02: Control Method Selection

Selects the Control Method (also referred to as the control mode) that the drive uses to operate the motor. Parameter A1-02

determines the control mode for motor 1 when the drive is set up to run two motors.

Note:

When changing control modes, all parameter settings depending upon the setting of A1-02 will be reset to the default.

i.5 Start-Up Programming and Operation

YASKAWA ELECTRIC TOEP C710636 04C U1000 Industrial MATRIX Drive Quick Start Guide

47