Setting 2: Drive Dedicated Motor (Speed Range for Constant Torque: 1:10)

Use this setting when operating a drive duty motor that allows constant torque in a speed range of 1:10. The drive will allow

the motor to run with 100% load from 10% up to 100% speed. Running at slower speeds with full load can trigger an overload

fault.

Overload Tolerance

Cooling Ability

Overload Characteristics

A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
C: Max. speed for 132MJ and below

Rated Speed=100% Speed

60 s

Continuous

A

B

C

Speed (%)

Torque (%)

100

150

110

100120 167 200

55

50

0

Motor is designed to effectively cool

itself even at low speeds.

Continuous operation with 100% load

from 6 Hz to E1-06, Motor Base

Frequency.

Setting 3: Vector Motor (Speed Range for Constant Torque: 1:100)

Use this setting when operating a drive-dedicated motor that allows constant torque in a speed range of 1:100. This motor type

is allowed to run with 100% load from 1% up to 100% speed. Running slower speeds with full load can trigger an overload

fault.

Overload Tolerance

Cooling Ability

Overload Characteristics

A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
C: Max. speed for 132MJ and below

150

100

90

50

0 1

100120 167 200

A

B

C

Continuous

Speed (%)

Rated Speed=100% Speed

Torque (%)

60 s

Motor is designed to effectively cool

itself at speeds near 0.6 Hz.

Continuous operation with 100% load

from 0.6 Hz to E1-06, Motor Base

Frequency.

Continuous operation below 0.6 Hz

may cause an oL1 or oL2 fault.

Setting 4: PM Derated Torque Motor

Use this setting when operating a PM motor. PM motors for derated torque have a self-cooling design and the overload tolerance

drops as the motor slows. Electronic thermal overload is triggered in accordance with the motor overload characteristics,

providing overheat protection across the entire speed range.

Overload Tolerance

Cooling Ability

Overload Characteristics

Continuous

60 s

Motor Speed (%)

Torque (%)

150

10

33

100

120
100

80

50

0.0

Motor is designed to produce 100%

torque at base speed. Built with

effective cooling capabilities.

Reaching 100% when operating at

below the base frequency causes a

motor overload fault (oL1). The drive

fault output closes and the motor coasts

to stop.

Setting 5: Constant Torque PM Motors (Constant Torque Range of 1:500)

Sets necessary protection characteristics when driving a PM with constant torque. These motors allow for a speed control from

0.2% to 100% when operating with 100% load. Slower speeds with 100% load will trigger overload.

i.5 Start-Up Programming and Operation