Yaskawa U1000 Industrial MATRIX Drive User Manual

Page 91

Advertising
background image

The “Safe Torque Off” state can only be achieved using the Safe Disable function. Removing the Run command stops the

drive and shuts the output off (baseblock), but does not create a “Safe Torque Off” status.

Note:

To avoid an uncontrolled stop during normal operation, make sure that the Safe Disable inputs are opened first when the motor has completely

stopped.

Returning to Normal Operation after Safe Disable

The Safe Disable function can only be deactivated when a Run command is not active.
If Safe Disable was activated during stop, turn on both Safe Disable inputs by deactivating “Safe Torque Off” to resume normal

operation.
If Safe Disable was activated during run, remove the Run command then turn on the Safe Disable inputs before restarting the

drive.

n

Safe Disable Monitor Output Function and Digital Operator Display

Table i.33

explains the drive output and Safe Disable monitor state depending on the Safe Disable inputs.

Table i.33 Safety Input and EDM Terminal Status

Safe Disable Input Status

Safe Disable Status Monitor,

(DM+, DM-)

Drive Output Status

Digital Operator

Display

Input 1, H1-HC

Input 2, H2-HC

S6 Switch = “N.O.”

S6 Switch = “N.C.”

OFF

OFF

OFF

ON

Safely disabled,

“Safe Torque Off”

Hbb (flashes)

ON

OFF

ON

OFF

Safely disabled,

“Safe Torque Off”

HbbF (flashes)

OFF

ON

ON

OFF

Safely disabled,

“Safe Torque Off”

HbbF (flashes)

ON

ON

ON

OFF

Baseblock,

ready for operation

Normal display

Safe Disable Status Monitor

Slide Switch S6 controls the polarity of this signal. Refer to

Table i.33

for functionality.

With the Safe Disable monitor output (terminals DM+ and DM-), the drive provides a safety status feedback signal. This signal

should be read by the device that controls the Safe Disable inputs (PLC or a safety relay) in order to prohibit leaving the “Safe

Torque Off” status in case the safety circuit malfunctions. Refer to the instruction manual of the safety device for details on

this function.

Digital Operator Display

When both Safe Disable inputs are open, “Hbb” will flash in the digital operator display.
If one Safe Disable channel is on while the other is off, “HbbF” will flash in the display to indicate that there is a problem in

the safety circuit or in the drive. This display should not appear under normal conditions if the Safe Disable circuit is utilized

properly.
If a fault in the safety circuit of the drive is detected, “SCF” will be displayed in the LCD operator. This indicates damage to

the drive.

n

Validating Safe Disable Function

Always perform the following validation test on the safe disable inputs after completing the wiring after start-up, when

replacing parts, or when conducting maintenance. Maintain check results as a record of tests performed.
• When the H1 and H2 signals turn OFF, confirm that “Hbb” is displayed on the LCD operator, and that the motor is not in

operation.

Monitor the ON/OFF status of the H1 and H2 signals and confirm the EDM signal according to

Table i.33

.

If the ON/OFF status of the signals do not match the display, it is possible that there is an error in the external device, the

external wiring is disconnected, there is a short circuit in the external wiring, or a failure in the drive. Find the cause and correct

the problem.
In normal operation, confirm the EDM signal according to

Table i.33

.

i.9 Standards Compliance