Digital Operator Display

Fault Name

dv4

Inversion Prevention Detection (CLV/PM control mode only)
Pulses indicate that the motor is rotating in the opposite direction of the speed reference. Set the number

of pulses to trigger inverse detection to F1-19.

Note:

Set F1-19 to 0 to disable inverse detection in applications where the motor may rotate in

the opposite direction of the speed reference.

dv7

Initial Polarity Estimation Timeout

dWAL

DriveWorksEZ Fault

dWFL

dWF1

EEPROM Memory DriveWorksEZ Data Error
There is an error in the DriveWorksEZ program saved to EEPROM.

E5

MECHATROLINK Watchdog Timer Error
The watchdog timed out.

EF0

Option Card External Fault
An external fault condition is present.

EF1

External Fault (input terminal S1)
External fault at multi-function input terminal S1.

EF2

External Fault (input terminal S2)
External fault at multi-function input terminal S2.

EF3

External Fault (input terminal S3)
External fault at multi-function input terminal S3.

EF4

External Fault (input terminal S4)
External fault at multi-function input terminal S4.

EF5

External Fault (input terminal S5)
External fault at multi-function input terminal S5.

EF6

External Fault (input terminal S6)
External fault at multi-function input terminal S6.

EF7

External Fault (input terminal S7)
External fault at multi-function input terminal S7.

EF8

External Fault (input terminal S8)
External fault at multi-function input terminal S8.

Err

EEPROM Write Error

Data cannot be written to the EEPROM

FAn

Fan fault
Fan failure

FbH

Excessive PID Feedback
PID feedback input is greater than the level set to b5-36 for longer than the time set to b5-37. Set b5-12

to 2 or 5 to enable fault detection.

FbL

PID Feedback Loss
PID feedback loss detection is programmed to trigger a fault (b5-12 = 2 or 5) and the PID feedback level

is below the detection level set to b5-13 for longer than the time set to b5-14.

Fdv

Power Supply Frequency Fault
The input power supply frequency exceeded the allowable frequency fluctuation.

GF

Ground Fault
• A current short to ground exceeded 50% of rated current on the output side of the drive.
• Setting L8-09 to 1 enables ground fault detection.

LF

Output Phase Loss
• Phase loss on the output side of the drive.
• Setting L8-07 to 1 or 2 enables Phase Loss Detection.