I.7 drive specifications – Yaskawa U1000 Industrial MATRIX Drive User Manual

Page 76

Advertising
background image

Item

Specification

Protection

Functions

Power Supply Regeneration Available

Motor Protection

Electronic thermal overload relay

Momentary Overcurrent

Protection

Drive stops when output current reaches about 200% of the rated current.

Overload Protection

Drive stops after 60 s at 150% of rated Heavy Duty output current

<3>

Overvoltage Protection

200 V class: Stops when input voltage exceeds approx. 315 V

400 V class: Stops when input voltage exceeds approx. 630 V

Undervoltage Protection

200 V class: Stops when input voltage falls below approx. 150 V

400 V class: Stops when input voltage falls below approx. 300 V

Momentary Power Loss

Ride-Thru

Immediately stop after 2 ms or longer power loss

<4>

Continuous operation during power loss shorter than 2 s (standard)

<5>

Heatsink Overheat Protection Thermistor

Stall Prevention

Stall Prevention is available during acceleration, deceleration, and during run.

Ground Protection

Electronic circuit protection

<6>

Charge LED of Capacitor for

Control Power Supply

Remains lit until control power supply voltage falls below 50 V

Environment

Area of Use

Indoors

Ambient Temperature

IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F)

IP00 enclosure: -10 °C to +50 °C (14 °F to 122 °F)

Humidity

95 RH% or less (no condensation)

Storage Temperature

-20 °C to +60 °C (short-term temperature during transportation)

Altitude

Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.

Vibration/Shock

10 to 20 Hz: 9.8 m/s

2

20 to 55 Hz: 5.9 m/s

2

(2o0028 to 2o0081 and 4o0011 to 4o0077)

2.0 m/s

2

(2o0104 to 2o0248 and 4o0096 to 4o0414)

Standard

• UL508C
• IEC/EN 61800-3, IEC/EN 61800-5-1
• ISO/EN 13849-1 Cat.3 PLe, IEC/EN 61508 SIL3

Protection Design

IP00/Open Type enclosure

<7>

, IP20/NEMA Type 1 enclosure

<1> Current derating is required. Select control modes in accordance with drive capacity.
<2> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors

and with changing motor temperature. Contact Yaskawa for consultation.

<3> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<4> Actual specifications may vary depending on motor characteristics.
<5> A separate Momentary Power Loss Ride-Thru Unit is required if the application needs to continue running for up to 2 seconds during a momentary

power loss.

<6> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground

fault is present at the output.

<7> Attaching the top protective cover and bottom cover on an IP00 enclosure drive will convert the drive to a NEMA Type 1 drive.

i.7 Drive Specifications

76

YASKAWA ELECTRIC TOEP C710636 04C U1000 Industrial MATRIX Drive Quick Start Guide