Ul standards compliance, Installation area – Yaskawa U1000 Industrial MATRIX Drive User Manual

Page 82

Advertising
background image

Three-Phase 200 V / 400 V Class

L3

L2

PE

L1

Drive

D

E

C

B

G

H

F

A

D

D

A

I

A – Ground the cable shield
B – Enclosure panel
C – Metal plate
D – Grounding surface (remove any

paint or sealant)

E – Drive

F – Motor cable (braided shield cable,

max. 10 m)

G – Motor
H – Cable clamp
I – Ground plate (scrape off any

visible paint)

Figure i.53 EMC Filter and Drive Installation for CE Compliance (Three-Phase 200 V / 400 V Class)

u

UL Standards Compliance

The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing and

evaluation, and determined that their stringent standards for product safety have been met. For a product to receive UL

certification, all components inside that product must also receive UL certification.

Figure i.54 UL/cUL Mark

This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions described

below must be met to maintain compliance when using this drive in combination with other equipment:

n

Installation Area

Do not install the drive to an area greater than pollution degree 2 (UL standard).

i.9 Standards Compliance