NOTICE: The analog signal wiring between the drive and the operator station or peripheral equipment should not exceed 50 meters when

using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system performance.

u

Sinking/Sourcing Mode for Digital Inputs

Use the wire jumper between terminals SC and SP or SC and SN to select between Sink mode, Source mode or external power

supply for the digital inputs S1 to S8 as shown in

Table i.11

(Default: Sink mode, internal power supply).

NOTICE: Do not short terminals SP and SN. Failure to comply will damage the drive.

Table i.11 Digital Input Sink/Source/External Power Supply Selection

Mode

Drive Internal Power Supply

(Terminals SN and SP)

External 24 Vdc Power Supply

Sinking Mode (NPN)

SC

S8

S7

24 Vdc

SP

SN

SC

S8

S7

24 Vdc

SP

SN

External

24 Vdc

Sourcing Mode (PNP)

SC

S8

S7

24 Vdc

SP

SN

SC

S8

S7

24 Vdc

SP

SN

External

24 Vdc

u

Sinking/Sourcing Mode Selection for Safe Disable Inputs

Use jumper S3 on the terminal board to select between Sink mode, Source mode or external power supply for the Safe Disable

inputs H1 and H2 as shown in

Table i.12

(Default: Source mode, internal power supply).

i.4 Electrical Installation

34

YASKAWA ELECTRIC TOEP C710636 04C U1000 Industrial MATRIX Drive Quick Start Guide