2.4 LED Indicator Specifications

2-5

2

2.4 LED Indicator Specifications

The LED indicator specifications for the 260IF Module are shown in the following table.

Table 2.3 LED Indicator Specifications

∗ 1.

The 260IF Module is offline for the two seconds from the completion

of the indicator test after startup through the completion of the MAC
ID duplication check. The 260IF Module is online after the MAC ID
duplication check at startup has been completed.

∗ 2.

When the network power supply is OFF, the 260IF Module automati-

cally resets as specified in the DeviceNet specifications even if a bus-
off error occurs. At the same time, the NS indicator will light red for a
moment and then go OFF again immediately. After power has been
restored to the network, the green NS indicator will start flashing
(online but not connected).

The following diagram shows the indicator test sequence that is performed immediately
after the power is turned ON. Check the ON and OFF status of these indicators for any mal-
functions. About 1 second is required for this test.

Fig 2.2 Display during Indicator Test

Indicator

Color

Status

Meaning

MS

Red/Green

Not lit
Lit green
Lit red

No power to the 260IF Module.
Operating normally.
Self-diagnostic error or WDT error.

NS

Red/green

Not lit
Flashing green
Lit green
Flashing red
Lit red

No power to the 260IF Module/offline.

*1

Online but not connected.
Online and connected.
No-DeviceNet communications error.
Communications not possible (duplicate MAC ID),
bus-off error, or WDT error.

*2

NS

MS

OFF

OFF

OFF

G

OFF

R

G

G

R

G

OFF

G

0.25 s

0.25 s

0.25 s

0.25 s

Power OFF

Device

startup

Start of

indicator test

1 s

End of

indicator test

Not lit

Not lit

Not lit

Not lit

Not lit

Green

Green

Green

Green

Green

Red

Red

0.25 s

0.25 s

0.25 s

0.25 s

Advertising