Wiring

7.1.3 Methods for Deciding the Power Supply Positioning

7-6

7

• Total length of power supply = 200 m
• Total current consumption = 0.2 A

+ 0.1 A + 0.05 A + 0.2 A + 0.15 A = 0.7 A

• Max. current according to the graph = 1.53 A

The total current consumption

< maximum current. Therefore, communications power can

be supplied to all nodes.

Example 2: Power Supply Positioned in the Middle of the Network

The following diagram shows the layout when the power supply is positioned in the middle
of the network and a thick cable with a total length of 200 m is used.

• Total power supply length on the left side = Total power supply length on the right

side=120 m

• Total current consumption on the left side = 0.2 A

+ 0.3 A + 0.1 A = 0.6 A

• Total current consumption on the right side = 0.25 A

+ 0.15 A + 0.1 A = 0.5 A

• Max. current on the left side according to the graph = Approx. 2.5 A
• Max. current on the right side according to the graph = Approx. 2.5 A

The total current consumption on the left side

< maximum current on the left side and the

total current consumption on the right side

< maximum current on the right side. Therefore,

communications power can be supplied to all nodes.

Calculation from the Formula

If the conditions cannot be met with simple calculation from the graph method, use the more
detailed method of calculation from the formula.

Formula

1. For separate communications and internal circuit power supplies

Terminating

resistance

Trunk line

Terminating

resistance

Communications

power supply

Node

Node

Node

Node

Node

0.2 A

0.1 A

0.05 A

0.2 A

0.15 A

200 m

: Trunk line

: Power supply

cable

Terminating

resistance

Trunk line

Trunk line

Node

Node

Node

Node

Node

Node

Terminating

resistance

0.2 A

0.3 A

0.1 A

0.25 A

0.15 A

0.1 A

Communications

power supply

120 m

120 m

: Power supply

cable

:Trunk line