4 inputs – Yaskawa 260IF DeviceNet System User Manual

Page 58

Advertising
background image

5.2 Message Send Function (MSG-SND)

5-9

5

Coil Offset (PARAM08)

Not used.

Input Relay Offset (PARAM09)

Not used.

Input Register Offset (PARAM10)

Not used.

Holding Register Offset (PARAM11)

Not used.

For System Use (PARAM12)

The channel number being used will be held.

Always set to 0000 Hex from the user program during the first scan when the power is
turned ON. After that, do not change the setting from the user program because this parame-
ter is used by the system.

5.2.4 Inputs

EXECUTE (Execute Send Command)

When this command is ON, the message will be sent.

This status must be held until COMPLETE (processing completed) or ERROR (error) turns
ON.

ABORT (Send Abort Command)

Aborts the message send. When this command is input, it has priority over EXECUTE (exe-
cute send command).

DEV-TYPE (Communications Device Type)

Designates the type of communications device. The setting is 11 for the 260IF Module.

PRO-TYPE (Communications Protocol)

Designates the communications protocol. The setting is 1 for the 260IF Module.

Note: In earlier versions, 1 meant MEMOBUS protocol, but 1 does not have

this meaning for the 260IF Module.