System Startup and Setup

4.1.5 I/O Allocations

4-6

4

4.1.5 I/O Allocations

After selecting the device and wiring the cables, allocate I/O to start 260IF Module commu-
nications.

The following flowchart shows the basic setting procedure using the CP-717 online func-
tions.

For details on basic CP-717 operation, refer to MP900 Series Machine Controller User's
Manual: Programming Panel Software
(Manual No.: SIEZ-C887-2.3, 2.4, to be prepared).

Connect the Programming Device

(CP-717 Engineering Tool) and the

MP920/MP940D with a communica-

Turn ON the communications power

supply.

Turn ON the Slave power supply.

The different power supplies can

be turned ON simultaneously.

Turn ON the MP920/MP940D power

supply.

Start the Programming Device

(CP-717).

In online mode, log on to the MP920/
MP940D.

Display the Module Configuration

Window.

Set “260IF” for the slot to which the

260IF Module is mounted.

Open the 216IF Definitions Window

and allocate the node addresses and

I/O registers for the connected

devices.

Close the Module Configuration

Window.

Check that the MS and NS indica-

tors on the 260IF Module are lit

Check that the MS and NS indica-

tors on the connected Slaves are lit

(green).

Refer to Machine Controller

MP900 Series Machine Controller

User's Manual: Programming

Panel Software

(Manual No.:

SIEZ-C887-2.3, 2.4, to be pre-

pared).

Refer to 4.3 260IF Module Setup and

MP900 Series Machine Controller

User's Manual: Programming Panel

Software

(Manual No.: SIEZ-C887-2.3,

2.4, to be prepared).

If the MS and NS indicators are

lit red or are flashing red, refer to

6.4 Troubleshooting.