Yaskawa 260IF DeviceNet System User Manual

Page 69

Advertising
background image

6.4 Troubleshooting

6-9

6

Table 6.4 Troubleshooting the Master (Cont’d)

Problem

Locations to Check

Probable

Cause

Possible Solution

Indicator

Status

I/O Status

No DeviceNet
communications
(cont’d)

MS lit green
NS not lit

1040

-

Communica-
tions power
supply error

1. Check the wiring and connections for

DeviceNet cables and connectors.

2. Check the power supply voltage and connection

for communications power supply.

3. Check the communications power supply

voltage for each DeviceNet connector on the
260IF Module (11 to 24V).

0002

0000

1. Check the wiring and connections for

DeviceNet cables and connectors.

2. Check the baud rate for each DeviceNet device

in the network.

3. Check the terminator (121

Ω) and connection

status.

4. Check the operation status of DeviceNet

devices on the network.

5. Replace the 260IF Module.

MS lit green
NS flashing
green

2004

0000

Connection not
established
with DeviceNet
device

Set the I/O allocations.

MS lit green
NS flashing
red

4004

404D

I/O sizes of
each DeviceNet
device are dif-
ferent from set-
ting.

1. Change the I/O sizes for the I/O allocations.
2. Change the I/O sizes for the DeviceNet device.

4004

404E

No response
from
DeviceNet
device.

1. Check the wiring and connections for

DeviceNet cables and connectors.

2. Check the baud rate for each DeviceNet device

in the network.

3. Check the power supply status of DeviceNet

devices on the network.

4004

4056

DeviceNet
device is idle.

Remove the cause of the idle status of the
DeviceNet device.

Communica-
tions are occur-
ring but the
maximum com-
munications
cycle time
exceeds the set-
ting.

MS lit green
NS lit green

8004

8000

Too much traf-
fic on
DeviceNet. The
communica-
tions cycle time
setting is too
low for the I/O
command send
time.

Set a longer communications cycle time.

Advertising