Yaskawa 260IF DeviceNet System User Manual

Page 73

Advertising
background image

6.4 Troubleshooting

6-13

6

Table 6.8 Troubleshooting Slaves (Cont’d)

Problem

Locations to Check

Probable

Cause

Possible Solution

Indicator

Status

I/O Status

No DeviceNet
communications
(cont’d)

MS lit green
NS flashing
red

4004

4000

No response
from
DeviceNet
Master

1. Check the wiring and connections for

DeviceNet cables and connectors.

2. Check the baud rate for each device.
3. Check the terminator (121

Ω) and connection

status.

4. Check the operation status of the DeviceNet

Master.

5. Check the power supply voltage and connection

for communications power supply.

6. Check the communications power supply

voltage for each DeviceNet connector on the
260IF Module (11 to 24V).

MS lit green
NS flashing
red

0000

0004

The switch
MAC ID set-
ting is different
from the MAC
ID setting
under the I/O
allocations.

1. Change the MAC ID setting under the I/O allo-

cations.

2. Change the switch MAC ID setting and cycle

the power.

MS lit green
NS lit green

0000

0004

The switch
MAC ID set-
ting is different
from the MAC
ID setting
under the I/O
allocations.

1. Change the MAC ID setting under the I/O allo-

cations.

2. Change the switch MAC ID setting and cycle

the power.

Communica-
tions are occur-
ring but the
receive data is
not being
refreshed.

MS lit green
NS lit green

8004

8003

DeviceNet
Master is in
idle status.

Remove the cause of the idle status of the
DeviceNet Master.

Communica-
tions are occur-
ring but the
receive data
refresh is
delayed.

MS lit green
NS lit green

8004

8003

Too much traf-
fic on
DeviceNet. The
communica-
tions cycle time
setting is too
low for the I/O
response
receive time.
The processing
load for data
exchange with
the PLC is too
large.

1. Increase communications cycle time for the

DeviceNet Master.

2. Reduce the baud rate.
3. Increase the CPU scan time for the I/O

allocation SCAN setting.