Network Maintenance

6.4.1 Masters

6-10

6

Table 6.5 Troubleshooting the Master (Cont’d)

Problem

Locations to Check

Probable

Cause

Possible Solution

Indicator

Status

I/O Status

Communica-
tions are occur-
ring but the
receive data
refresh is
delayed.

MS lit green
NS lit green

8004

8000

Too much traf-
fic on
DeviceNet.
The communi-
cations cycle
time setting is
too low for the
I/O response
receive time.
The processing
load for data
exchange with
the PLC is too
large.

1. Set a longer communications cycle time.
2. Reduce the baud rate.
3. Increase the setting of the CPU scan time for

the I/O allocation SCAN setting.

MSG-SND func-
tion terminated
due to error.
(during
DeviceNet com-
munications)

MS lit green
NS lit green

8004

8000

Parameter set-
ting error

Check that the MSG-SND function parameter set-
tings are correct.

• Data address
• Data size

MS lit green
NS flashing
green

2004

-

EM allocations
not made.

Set the EM allocation under I/O Allocations.

MS lit green
NS lit red

4004

40XX

I/O communi-
cations error

Remove the cause of the I/O communications error.

MSG-SND func-
tion remains
BUSY and does
not end.

MS lit green
NS lit green

8004

8000

MSG-SND
function
parameter set-
ting error

Check that the MSG-SND function parameter set-
tings are correct.

• Remote station number

Too much traf-
fic on
DeviceNet
(Cannot send
Explicit request
message.)

1. Set longer communications cycle time.
2. For multi-Master configuration, increase the

communications cycle time for other Master.