Yaskawa 260IF DeviceNet System User Manual

Page 72

Advertising
background image

Network Maintenance

6.4.2 Slaves

6-12

6

Table 6.7 Troubleshooting Slaves (Cont’d)

Problem

Locations to Check

Probable

Cause

Possible Solution

Indicator

Status

I/O Status

No DeviceNet
communications
(cont’d)

MS lit green
NS not lit

1040

-

• Communica-

tions power
supply error

• DeviceNet

network
error

1. Check the wiring and connections for

DeviceNet cables and connectors.

2. Check the power supply voltage and connection

for communications power supply.

3. Check the communications power supply

voltage for each DeviceNet connector on the
260IF Module (11 to 24 V).

4. Check the terminator (121

Ω) and connection

status.

MS lit red
NS not lit

0002

0000

DeviceNet net-
work error

1. Check the wiring and connections for

DeviceNet cables and connectors.

2. Check the baud rate for each device.
3. Check the terminator (121

Ω) and connection

status.

4. Check the operation status of the DeviceNet

Master.

5. Replace the 260IF Module.

MS lit green
NS flashing
green

2004

0000

Connection not
established
with DeviceNet
device

1. Check the DeviceNet Master scan list settings.
2. Check the wiring and connections for

DeviceNet cables and connectors.

3. Check the baud rate for each device.
4. Check the operation status of the DeviceNet

Master.

DeviceNet I/O
size different
from setting

1. Change the I/O sizes for the I/O allocations.
2. Change the I/O sizes for the DeviceNet Master.

MS lit green
NS flashing
green

4004

4000

No response
from
DeviceNet
Master

1. Check the wiring and connections for

DeviceNet cables and connectors.

2. Check the baud rate for each device.
3. Check the terminator (121

Ω) and connection

status.

4. Check the operation status of the DeviceNet

Master.

5. Check the power supply voltage and connection

for communications power supply.

6. Check the communications power supply

voltage for each DeviceNet connector on the
260IF Module (11 to 24 V).