System Startup and Setup

4.2.2 Calculating Communications Cycle Times

4-8

4

3. Slaves with 8 bytes or less of both input and output data

[94 + 8(No + Ni)]

× Tb + 600[µs]

4. Slaves with 8 bytes or more of output data

[111×TRUNC(No/7)]

× Tb

+ [94 + 8

× MOD(No/7)] × Tb

+ 300

× [TRUNC(No/7) + 1][µs]

Note: When MOD(No/7) = 0, the 3rd line of the equation will be " + 300

×

TRUNC(No/7)."

5. Slaves with 8 bytes or more of input data

[111

× TRUNC(Ni/7)] × Tb

+ [94 + 8

× MOD (Ni/7)]×Tb

+ 300

× [TRUNC(Ni/7) + 1] [µs]

Note: When MOD(Ni/7) = 0, the 3rd line of the equation will be " + 300

×

TRUNC(Ni/7)."

6. Slaves with 8 bytes or more of both input and output data

[111

× TRUNC(Ni/7)] × Tb

+ [94 + 8

× MOD(Ni/7)] × Tb

+ 300

× [TRUNC(Ni/7) + 1]

+ [111

× TRUNC(No/7)] × Tb

+ [94 + 8

× MOD(No/7)] × Tb

+ 300

× [TRUNC(No/7) + 1] [µs]

Note: 1. When MOD(Ni/7) = 0, the 3rd line of the equation will be " + 300

× TRUNC(Ni/7)."

2. When MOD(No/7) = 0, the 6th line of the equation will be " + 300

× TRUNC(No/7)."

7. Slaves with 8 bytes or less of input data and 8 bytes or more of output data

[47 + 8

× Ni] × Tb

+ 300
+ [111

× TRUNC(No/7)] × Tb

+ [94 + 8

× MOD(No/7)] × Tb

+ 300

× [TRUNC(No/7) + 1]

Note: When MOD(No/7) = 0, the 5th line of the equation will be " + 300

×

TRUNC(No/7)."

8. Slaves with 8 bytes or more of input data and 8 bytes or less of output data

[111

× TRUNC(Ni/7)] × Tb

+ [94 + 8

× MOD(Ni/7)] × Tb

+ 300

× [TRUNC(Ni/7) + 1]

+ [47 + 8

× No] × Tb

+ 300

Note: When MOD(Ni/7) = 0, the 3rd line of the equation will be " + 300

×

TRUNC(Ni/7)."