Technical data

Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN

Page 11

4

Technical data

4.1

Electrical data

Input levels

XP200-HV TL

XP250-HV TL

XP350-HV TL

Max. PV generator power [kW]

240

300

420

MPPT range [V]

450 ... 830

No-load voltage [V]

1000*

Monitoring of input voltage [V]

Stand-by from V

on

> 300

Night shutdown from V

off

< 250

MPP starting voltage V

start

> 600

Voltage ripple [%]

< 3

Current ripple [%]

< 4

Max. input current [A]

467

611

856

Output levels

XP200-HV TL

XP250-HV TL

XP350-HV TL

Rated power [kW]

200

250

350

Max. power [kW]

200

250

350

Line voltage

In accordance with country-specific guidelines

Output voltage [V]

290 (±10%)

Rated current [A]

398

498

697

Max. current [A]

398

498

697

Rated frequency [Hz]

50/60

cos phi

0.80 inductive ... 0.80 capacitive

Distortion factor [%]

< 3 at rated power

Fault signal relay

Potential-free NO contact, max. 30 V/1 A

S0 output

Open collector output, max. 30 V/50 mA

General electrical data

XP200-HV TL

XP250-HV TL

XP350-HV TL

Max. efficiency [%]

98.2

98.1

98.3

European efficiency [%]

97.8

97.8

98.0

Internal consumption in

standby mode [W]

< 80

Internal consumption in operation [W]

< 360

Min. grid feed power [W]

10 000

Grid monitoring

In accordance with country-specific guidelines

CE conformity

yes

Table 1:

Electrical data of the inverter

*