10.2 Operating states

Fault

Disconnected,

system stop

Connect the PV

generator

Connect the

power grid

Initialise

MPP

MPPT

MPP

Start

[Vpv > Vmpp_min (450 V)

and T > 5 sec]

[Outside of target range]

[T > 8 sec]

[Vpv =

MPP Ref.]

Serious fault

Inverter ON

Fault reset

Inverter OFF

[Ppv < Pstop (10 sec)]

[Vpv ≥ Vpv_start and

T > Tstart (300 sec)]

[Vpv ≥ 400 V and T > 5 sec]

Figure 70: Overview of operating states

Key

MPPT

Maximum Power Point Tracker

Tstart

Minimum time for which Vpv must be greater

than Vpv_start

Vpv

Voltage in the PV generator

MPP ref.

PV voltage reference

VMPP min Minimum voltage of the MPP

Ppv

PV power

Vpv_start

Starting voltage in the PV generator

Pstop

Power level at which the feed-in is interrupted