KACO Powador XP200-HV TL User Manual

Page 80

Advertising
background image

Maintenance/Cleaning

Page 80

Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN

Recommended

maintenance intervals

Maintenance work

6 months*

Cleaning or replacement

Filter mats in the air intake filters

Cleaning

Inside of the cabinet
Fans

6 months

Function check

Emergency stop (OFF)

12 months*

Cleaning

Power section of the heat sink

12 months

Visual inspection

Contact connections
Fuses
Switches
Overvoltage protection
Redundant auxiliary power supplies
Check all parts in the cabinet for

Heavy dust deposits and soiling

Moisture (especially water that has permea-

ted from the outside)

Visual inspection (and

replacement, if necessary)

All warning labels

Function check

Fans
Door contacts
Operating lights and fault lights

*If heavy soiling is present at the installation location, you may need to shorten the maintenance interval.

Table 30: Maintenance intervals

Advertising