8.5.7 Controller Parameters

Parameter

Unit

Range

Description

Factory settings

VC P gain

0 ... 999.99

P gain of PV voltage controller

5

VC I gain

0 ... 999.99

I gain PV voltage controller

10

Voltage detection

LPF

Hz

0 ... 9999

Grid voltage and inverter voltage

filter of dq axis

100

CC P gain

0 ... 999.99

P gain of inverter output current con-

troller

Device-specific

CC I gain

0 ... 999.99

I gain of inverter output current con-

troller

Device-specific

CC di/dt

p.u.

1 ... 9999

Slope of inverter rated current gene-

ration

500

Ramp

ms

0 ... 99999

Slope of PV voltage generation (time

for 100 V change)

2500

Li

µH

0 ... 99999

Inductance value of inverter output

LC filter

Device-specific

Vdc Reference

V DC

0 ... 999.9

DC voltage reference when it is not in

MPPT range

Device-specific

CC Period

µs

100 ... 400

Inverter switching frequency

333

PLL P Gain

0 ... 999.99

P Gain if grid voltage PLL

0.05

PLL I Gain

0 ... 999.99

I Gain if grid voltage PLL

0.02

Auto Fault Reset

Count

times

0 ... 20

Maximum count of auto reset func-

tion

7

Heatsink OT Level

°C

50 ... 150

Maximum value of PEBB temperature

85

Power Compensa-

tion

-

0 ... 1

Power compensation for MPPT con-

trol

0

Test mode

0 ... 99999

Value for function test mode

0

Options

0 ... 99999

Outside option board setup

0

Deviation Tolerance

Time

20 ms

0 ... 25

Level 1 trip time when level 2 protec-

tion is disabled

3

Reactive Power

Compensation

%

–30 ... 30

Control value for reactive power

degree of accuracy

0

Variable MPP Vmin

Enb

On(1), Off(0)

Setup value for inverter operation

rage maximisation

1

T_CLOUD

s

0 ... 3600

Time for declines of PV generation

due to cloud

Device-specific

T_CLOUD_CNT

0 ... 20

Count for declines of PV generation

due to cloud

3

Remote Power

Control

%

0 ... 100

Inverter active power which can be

controlled from outside device

100

PEBB2 Temperature

°C

0 ... 150

PEBB2 temperature (read only)

PEBB3 Temperature

°C

0 ... 150

PEBB3 temperature (read only)