Installation

Page 30

Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN

Electrician

"

A terminating resistor (120 Ω, 0.5 W, 1 %) is installed on the main control board (XCU).

For termination disposal use a jumper between RS485 A1 (1a) and RS485 C1 (2b).

Signal transceiver

-RS485

GND

A(DATA–)

Jumper

B(DATA+)

1b 2b 3b 4b

1a 2a 3a 4a

Figure 25: RS485-1 termination disposal

NOTE

Terminating resistors need to be installed at both ends of the device within the communication

railroad.