Faults and Warnings

Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN

Page 83

Replacing the outlet filter (Figure 73)
1. On the inside of the open front door press the

hooks (item 4) of the outlet filter.

2. Push the outlet filter towards the front side of the

door.

3. Remove the outlet filter.
4. Mount the new outlet filter in reverse order.
5. Ensure that all hooks of the outlet filter are snap-

ped in.

4

Figure 73: Replacing the outlet filter

Finishing the maintenance of the outlet filter
1. Close the front doors of the inverter.
2. Switch on the inverter (see section 11 on page 79).

12

Faults and Warnings

If a problem occurs in the system, the inverter notifies you using an audible signal and a display using the MMI soft-

ware. With the Powador XP200-HV or Powador XP250-HV, two types of problems are displayed: faults and warnings.
A fault is a serious problem that causes the inverter to stop. Faults are displayed on the MMI screen and are highligh-

ted in red. A warning represents a more minor problem. When a warning occurs, the system does not cease opera-

tion. Warnings are displayed in yellow. Fault types and descriptions are listed in the following tables.

12.1 Warnings

Message

Code

Description

SP1 (PV SP) Failure

W01

Failure of surge (overvoltage) protector SP1 on the PV side

PV Fuse Failure

W03

Fuse failure on the PV side (optional)

Ground Fault Warning

W04

The insulation resistance of the PV module falls below the

limit value specified for alert 1 under ground fault monitoring

(optional).

PV Over Voltage Warning

W05

PV voltage > parameter [PV Operate Level]

PEBB Over Temp. Warning

W20

Temperature of the heatsink for the PEBB (power electronics

building block) >75°C

PEBB Fan Failure

W21

Failure of the fan on the heatsink for the PEBB (power electro-

nics building block)

SP2 (Grid SP) Failure

W30

Failure of surge (overvoltage) protector SP2 on the grid side

ASYNC Warning

W111

Voltage built up at inverter side is asynchronous with the grid

Test Mode

W40

The system is working in test mode.

Watchdog Failure

W41

Watchdog function worked and system rebooted.

Cabinet Over Temp. Warning

W50

The temperature in the cabinet exceeds the parameter [Cabi-

net temperature maximum].

Table 31: Warnings