Specifications

94

5.2

Environmental Conditions

Table 12

Specifications applicable to environment

Enclosure

The UPS is housed in a NEMA-1 enclosure. The enclosure is designed for indoor use only

and is not to be subjected to falling objects or precipitation.

Recommended Operating

Temperature

25°C ambient

Maximum Operating

Temperature

40°C ambient (design temperature) without derating; (see Notes 1-3).

Minimum Operating

Temperature

0°C

Storage Temperature

-20°C to 70°C

Typical Battery

Temperature Requirements

Average annual temperature shall not exceed 27°C. Peak temperature shall not exceed

43°C during any 24-hour period. See battery manufacturer’s recommendations.

Relative Humidity

0 to 95% without condensation

Operating Elevation

Sea level to 1219 meters (4000 ft.) without derating

Storage Elevation

Sea level to 15,000 meters (50,000 ft.)

Audible Noise, measured

5 feet from unit

62-69 dBA typical for 100-450kVA units

72 dBA typical for 500-750kVA units

75 dBA typical for 1000kVA units

Derating for Higher

Ambient Temperatures

(see Note 3)

98% at 45°C
96% at 50°C
93% at 55°C
Consult your Liebert sales representative regarding applications in high ambient

temperatures or call 1-800-LIEBERT. Special temperature sensors must be installed at the

factory.

Derating for Higher

Elevations

(see Note 4)

Elevation-ft. (m)

% Derating @ 104°F (40°C)

Ambient (see Note 3)

% Derating @ 95°F (35°C)

Ambient (see Note 3)

5000 (1524)

98%

100%

5249 (1600)

98%

100%

5906 (1800)

97%

99%

6562 (2000)

96%

98%

7218 (2200)

95%

97%

7874 (2400)

94%

96%

8530 (2600)

93%

95%

9186 (2800)

92%

94%

9843 (3000)

90%

92%

NOTES
1. This category of electronic equipment is agency rated for use in an atmosphere free of conductive particles. Some industrial facilities

may require a room air filtration system to keep the UPS free of excess moisture and contaminants.

2. The UPS system is designed to operate continuously at 40°C. However, design equipment life expectancy will be extended with lower

temperatures (25°C is recommended).

3. Ambient temperature is the maximum ambient temperature during any 24-hour period. For operation at higher temperatures, consult

your Liebert sales representative or call Liebert Global Services at 1-800-LIEBERT.

4. Exercise care during installation to ensure unimpeded airflow through the UPS system. For operation at higher elevations, consult your

Liebert sales representative or call Liebert Global Services at 1-800-LIEBERT.