0 specifications, 1 rating, Pecifications – Liebert 610 User Manual

Page 99: Rating

Advertising
background image

Specifications

93

5.0

S

PECIFICATIONS

5.1

Rating

The kVA and kW ratings and the nominal voltages and currents for continuous operation are listed on

the unit nameplates (inside Operator Control Panel door) and on the System One-Line Diagram. The

rated output power envelope of the UPS is illustrated in Figure 59. The UPS is rated to deliver rated

kVA and rated kW at 0.8 lagging power factor (pf), or 0.9 lagging pf for some models. However, the

UPS will operate connected loads with power factors ranging from 0.7 lagging through 1.0 (unity).
Connected load kW and kVA are both displayed on the LCD screen when the UPS is powering the

load. The approximate connected load power factor may be easily calculated by kW ÷ kVA = pf.
For load power factors between 0.7 lagging and the rated power factor (usually 0.8 or 0.9), the full

kVA rating of the unit is available. However, above the rated pf the kW rating will become the limit-

ing factor. Note that some models are specifically rated for a 0.9 lagging output power factor.
For loads with power factors below 0.7 lagging or with leading power factors, the UPS output is kVA

limited and the UPS System may not meet all of its output performance specifications. Contact Lie-

bert Global Services at 1-800-LIEBERT to request assistance for these applications.

Figure 59 Output power envelope for 0.8 and 0.9 pf rated units

LAGGING

power factor (pf)

LEADING

power factor (pf)

Contact Liebert for

load operation in this

area

0.8

0.7

0.9

1.0

kW

Contact Liebert for

load operation in this

area

0.9 x kVA

0.8 x kVA

0.7 x kVA

Rated