Present status, Figure 14 present status report screens, Event history – Liebert 610 User Manual

Page 34: Figure 15 event history report screen

Advertising
background image

Operation

28

Present Status

The Present Status screen shows the current status of the UPS module. This screen displays any

alarm messages that are present and the values of the metered parameters for each cabinet.
Each update sequence (every 4 milliseconds) is called a frame. The frame number is displayed in the

upper right corner. The Present Status screen display is updated every two seconds.
Battery Time Remaining (in minutes) is displayed on the module screens during a battery discharge.

The value is on the Battery Volts line in the TIME column (far right side of the screen). For the first

two minutes of discharge, the Rated Time Remaining is displayed. After that, the Calculated Time

Remaining is displayed and updated every six seconds.
All the information on this screen, including Battery Time Remaining, is available to a local terminal

or modem through the communications ports provided in the Series 610 UPS. Refer to Table 6 in this

manual for keyboard commands to use with the communication ports.

Figure 14 Present status report screens

Event History

The Event History screen lists the active alarms present in the UPS. This screen also displays the

prior 128 alarm frames, in a first in, first out (FIFO) sequence, that have taken place along with the

date and the time that each alarm frame occurred. Use the Up and Down pads to look through the

different alarm frames.

Figure 15 Event history report screen

PRESENT STATUS MODULE-0 01/12/96 14:06:26 FRAME 35
ORDER - 000000 SITE ID - 00000 SITE TAG - 0000000
**** ACTIVE ALARMS **** Batt Discharging

OUTPUT VOLTS

OUTPUT AMPS

OUTPUT FREQUENCY

BATTERY VOLTS

BATTERY AMPS

INPUT VOLTS

INPUT AMPS

LOAD KVA

END OF REPORT

A

480

325

0

0

DC

480

-645

B

480

325

0

0

TIME

0:09

LOAD

270

C

480

325

0

0

HERTZ

60.0

EXIT

SELECT :

EVENT HISTORY MODULE-0 01/17/96 11:23:41 FRAME 175
ORDER - 000000 SITE ID - 00000 SITE TAG - 0000000
**** ACTIVE ALARMS **** Batt Discharging Low Batt Warning

NEXT FRAME

PREVIOUS FRAME

EXIT

UP :

DOWN :

SELECT :

Advertising